Product description


8 DI/6 DO, AC220 or DC24V power supply

Support power-off retentive
Support basic logic control and data operation
Support high speed count, pulse output, external interruption, C language function block, free switch for I/O points, free protocol communication and MODBUS communication.

Can not support expansion module and BD board.


Item  Specification  

Insulation Voltage Above DC 500V 2MΩ  

Noise Resistance 1000V 1uS pulse for 1 minute  

Environment Temperature 0~60  

Ambient Humidity 5%~95%  

COM 1 RS-232, be connected to host machine or HMI for programming or debugging  

COM 2 RS-485 or RS-232,network or connect to intelligent instrument, inverter, etc.  

Installation M3 screw fixed or DIN46277 (35mm width) guide rail installation  

Grounding The third type grounding (Never perform common grounding with strong power system)  


Functional Specifications   

Program Operation Mode

Circulation scanning mode, timing scanning mode  


Program Mode  

Instructions and ladder chart  


Dispose Speed  0.5us  


Power Failure Holding  FlashROM  


User Program’s Capacity  2500 steps  

I/O Points  8 input points,6 output points  

Output Format  Relay  

Interior Coil’s Points (M)  8512 points  


Timer - Points 620 points  

100mS timer:set time 0.1~3276.7 seconds

10mS timer:set time 0.01~327.67 seconds

1mS timer:set time 0.001~32.767 seconds  


Counter - Points 635 Points   

16 bits counter::Set value K0~32767

32 bits counter:Set value K0~2147483647  


Data Register(D)  8512 characters  


FlashROM Register(FD)  2048 characters  


High-speed Count Format  High speed counter, pulse output, exterior interruption  


Timing Scanning Interval Setting  1~99mS  


Password Protection  6 characters ASCII  


Self-diagnose Function  Power on self-diagnose, monitor timer, grammar check  



XC3-14 8DI/6DO

XC3-24 14DI/10DO

XC3-48 18DI/14DO

XC3-48 28DI/20DO